Publication CNET-IN003A-EN-P - January 2006

Overview of the ControlNet Ex Media System 1-11

UL, cUL I/O Entity Parameters and Requirements

The entity concept allows interconnection of intrinsically-safe
apparatus with associated apparatus not specifically examined in
combination as a system when the approved values of V

oc

and I

sc

or V

t

and I

t

of the associated apparatus are less than or equal to V

max

and

I

max

of the intrinsically-safe apparatus and the approved values of C

a

and L

a

of the associated apparatus are greater than C

i

+ C

cable

and L

i

+

L

cable

respectively for the intrinsically-safe apparatus.

Wiring methods must be in accordance with the National Electric
Code, ANSI/NFPA 70, Article 504 and 505 or the Canadian Electric
Code CSA C22.1, Part 1, Appendix F. For additional information refer
to ANSI/ISA RP12.6.

TIP

For more information on UL and cUL installation
requirements, refer to publication 1797-RM001, FLEX
Ex System Certification Reference Manual.

Terminals

V

t

(V)

I

t

(mA)

Groups

C

a

(

µ

F)

L

a

(

µ

H)

Male Bus Connector

5.8

400

A-G

3.0

3.0

WARNING

Substitution of components may impair the intrinsic
safety of this system.

AVERTISSEMENT: La substitution de composant peut
compromettre la securite intrinseque.