3-16 Install a ControlNet Ex Media System
6. After you have moved the chamber gauge ring to the last
position and turned the strip tool the final time:
a. Move the chamber-gauge ring backward to release the strip
tool and remove it from the cable.
b. Slip the crimp ferrule onto the cable. Push it back to the
sheath area of the cable to keep it out of the way for the
moment.
c. Strip away the appropriate portion of the cable without using
the strip tool.
d. Clean the cable parts that remain from the strip chamber after
each use.
Be sure to strip the cable to expose these layers of the cable:
Crimp Ferrule
Cable
41887a
All Four Shield Layers
Braid/Tape/Braid/Tape
White Foam Electric
Or 1st Tape, If Tape
Is Bonded
Center
Conductor
8.3 mm (0.33 in.)
3.7 mm (0.15 in.)
4.0 mm (0.16 in.)
20076a