3-6 Install a ControlNet Ex Media System

Mount a Tap Through the Body Holes

Mount the tap to a suitable fixture by using a tie wrap, or screws and
flat washers.

Specifications

The following table lists the specifications for the ControlNet Ex taps.

Install Fiber Hubs

Read the following sections before installing a fiber repeater hub.

TIP

A suitable fixture (mounting surface) can be
conductive or grounded because the mounting holes
are electrically isolated.

Body Holes

Body Holes

Tie Wrap

Screws and Flat Washers

You can use a variety of screw types.

Tie Wrap

Screws and Flat Washers

(Not Supplied)

41645

41646

ATTENTION

Do not over-tighten the screws. Over-tightening the
screws can damage the tap. The applied torque
should be 0.2-0.4 Nm (1-2 ft-lbs). Do not use screws
larger than #8 in these holes.

Operating temperature -20 to 70 °C (-4 to 158 °F)
Storage temperature

-40 to 85 °C (-40 to 185 °F)

Relative humidity

5 to 95% noncondensing

To Install a Fiber Repeater Hub, You Should

See Page

Apply the Installation in Zone 1 and related intrinsically-safe
warnings and standards

3-7

Select where to mount the fiber repeater hub

3-8

Mount the fiber repeater hub

3-9