Estimate Fiber Media
Lengths

The maximum length of a fiber media section for the 1797-RPFM
module is dependent on the quality of the fiber, number of splices,
and the number of connectors. The total attenuation for a cable
section must be less than 13.3 dB.

Typically, cable attenuation for a wavelength of 1300 nm is less than

1.5 dB/km.

Determine How Many Trunk
Terminators You Need

You must use 75

trunk terminators equipped with intrinsically-safe

insulators (cat. no. 1797-XT) at the end of each segment in the
ControlNet Ex cable system.

500 m
(1640 ft)

250 m
(820 ft)

2

20

Number of Taps With One FLEX Ex Redundant ControlNet Barrier Module

Seg

m

ent

Lengt

h

m (f

t)

IMPORTANT

Avoid joining cable with connectors as much as
possible. Connectors can cause considerable
attenuation and limit the maximum length of your
system. Be sure to check the attenuation of each
cable sections after the cable is installed.