Install a ControlNet Ex Media System 3-17
Be sure to strip the cable to expose these layers of the cable:
7. If you are using plenum FEP cable, cut off an additional 3.1mm
(approximately 1/8 in.) of the outer sheath with the knife from
the toolkit.
8. Be certain that the center conductor meausures 4.0 mm (0.16 in.)
in length.
IMPORTANT
If you do not see the three distinct layers of cable or
if the outer braid has been scored or cut, snip off the
exposed end with the wire cutters and repeat the
entire cable-stripping process. It is very important
that the outer braid be intact before you crimp the
connector.
If You Are
Using
Go To Step
FEP cable
7
PVC cable
8
All Four Shield Layers
Braid/Tape/Braid/Tape
White Foam Electric
Or 1st Tape, If Tape
Is Bonded
Center
Conductor
8.3 mm (0.33 in.)
3.7 mm (0.15 in.)
4.0 mm (0.16 in.)
20076a
All Four Shield Layers
Braid/Tape/Braid/Tape
White Insulation Or
1st Tape
Center
Conductor
Sheath
11.44 mm (0.45 in.)
3.7 mm (0.15 in.)
4.0 mm (0.16 in.)
20076a