2-18 Plan a ControlNet Ex Media System

Plan Your Network

Refer to this list when you plan your network.

Maximum of 99 nodes (excluding fiber repeater hubs)

Fiber repeater hubs require a tap but are not counted as nodes
(they are included in the number of devices allowed per
segment [48])

Fiber repeater hubs may be installed at any tap location along a
segment

There can be only one path between any two points on a
network

The configuration of both sides of a redundant segment must be
the same

The total cable difference between the two sides of a redundant
network cannot exceed 800 m (2640 ft)

Order Parts

The following table contains a list of ControlNet Ex Components.
Refer to the ControlNet and ControlNet Ex Media System Components
List, publication AG-PA002, for a list of other ControlNet parts.

Item

Cat. No.

Guidelines

Required Quantity

1

Taps

Straight T-tap

Straight Y-tap

Right-angle T-tap

Right-angle Y-tap

1797-TPS

1797-TPYS

1797-TPR

1797-TPYR

You need a tap for each connection to the
trunk cable (nodes and repeaters).

Each tap kit contains: two BNC connector
kits, one dust cap, one universal mounting
bracket, ControlNet Ex cable labels and
two screws

Number of repeaters x 2

+

Number of nodes

Trunk Terminators

1797-XT

(quantity of 50)

You need a terminator for each end

of each segment.

Number of segments x 2

Trunk Cable

Use the ControlNet Ex Media System

Component List, publication AG-PA002,

to order your required length of cable.

Follow guidelines on page 2-4

of this document to determine
cable length

Tap Terminator

1797-TCAP

(quantity of 5)

Use the dummy load to plug into drop
cables that are not attached to a node.

One for every drop cable that is
not attached to a node