Publication CNET-IN003A-EN-P - January 2006

Plan a ControlNet Ex Media System 2-13

Application Considerations

The following guidelines coincide with the guidelines for the
installation of electrical equipment to minimize electrical noise inputs
to controllers from external sources contained in IEEE standard
518-1982. When planning your cable system keep these installation
considerations in mind.

Understand Conductor Categories

Conductors can be divided into three categories.

ATTENTION

These guidelines apply only to noise coupling.
Intrinsic safety requirements for cable mounting are
of the highest priority.

Category

Includes

1

ac power lines

High-power digital ac I/O lines

High-power digital dc I/O lines

Power connections (conductors) from motion drives to motors

2

Analog I/O lines and dc power lines for analog circuits

Low-power digital ac/dc I/O lines

Low-power digital I/O lines

ControlNet Ex communication cables

3

Low-voltage dc power lines

Communication cables to connect between system components
within the same enclosure