Publication CNET-IN003A-EN-P - January 2006

Install a ControlNet Ex Media System 3-29

3. Ensure the locking tabs snap into place.

4. Remove the insulator boot from the terminals.

5. Connect the trunk cable as shown in the illustration.

a. Connect the ControlNet trunk cable to the Channel A output

connector (1).

b. Connect the redundant ControlNet trunk cable to the Channel

B output connector (2).

c. Connect the ControlNet trunk cable to the Channel A input

connector (3).

d. Connect the redundant ControlNet trunk cable to the Channel

B input connector (4).

6. Install a direct ground wire with a minimum diameter of 4 mm

2

between terminal 5 and the PA Ground (Equipotential System)
in the hazardous area where the ControlNet Ex coax cable is
installed.

IMPORTANT

Connect the ControlNet Ex side of the barrier
module to either a 1797-ACNR15 FLEX Ex I/O
module or a 1797-TCAP FLEX Ex Safe Tap Dummy
Load using only ControlNet Ex Taps (such as
1797-TPR, 1797-TPYR, 1797-TPS, or 1797-TPYS).

IMPORTANT

Do not connect terminal 5 or the DIN rail to a
standard earth ground connection in the safe area.

In

Out

Out

Channel A

Channel B

In

3

1

2

4

30502-mdin

5

ControlNet Trunk Cables