Install a ControlNet Ex Media System 3-19

Test for Electrical Shorts and Continuity Between the Center
Conductor and the Shield

1. The NetLinx Media Checker (catalog number 1788-MCHKR) is

the preferred tool for continuity testing. Attach the connector
end of the cable to the port on top of the media checker.

2. As a secondary method, you can also use an ohmmeter or

continuity tester to test for a short between the connector body
and pin.

3. Use shorting clips to connect a temporary short between the pin

and connector body at one end of the cable.

4. At the other end of the cable, use the media checker, an

ohmmeter, or continuity tester to test for electrical continuity.

If Resistance Reading Indicates

Then

That a short exists

Continue to next section

There is no short

Use your wire cutters to cut off the
connector, install a new connector
and begin testing again

31195-M

LENGTH

WIRE MAP

TEST

SETUP

ENTER

OFF

MediaChecker

1788-MCHKR

Attach the connector end of the
cable to the port on top of the
media checker.

20166

Connector Body

Pin