Plan a ControlNet Ex Media System 2-17

Order Components

Now that you are ready to begin ordering components, use these
guidelines to help you select components.

General Planning

The ControlNet Ex cable system is isolated from earth and must be
protected from inadvertent ground connections.

Plan a Segment

Refer to this list when you plan a segment.

All connections to the trunk cable require a tap

Taps may be installed at any location on the trunk cable

Tap drop-cable length must not be changed

Maximum number of taps = 48, with 250 m (820 ft) of standard
RG-6 trunk cable

Maximum trunk cable length of RG-6 trunk cable = 1000 m
(3280 ft), with 2 taps

75

trunk terminators are required on both ends

One tap with an unconnected drop cable may be installed for
maintenance purposes

Use BNC bullet connectors at future tap locations

Do not mix redundant and non-redundant nodes

Use ControlNet Ex tap terminators (1797-TCAP) for all other
unconnected drop cables

Avoid high noise environments when routing cables

A supplied ferrite toroid should be used on the ControlNet Ex
trunk as it enters and leaves control cabinets