Rockwell Automation DeviceLogix System User Manual User Manual
Page 194

194
Publication RA-UM003B-EN-P - February 2010
Appendix B RSNetWorx for DeviceNet Software and the DeviceLogix Editors
To the change the network status override:
1. Click the current value of the Network Status Override
parameter.
The field turns into a drop-down list box.
2. Click the arrow to display the values.
3. Click the desired value.
4. Click Apply to save the new value without closing the window.
Or click OK to save the new value and to close the window.
Download to a Device That Is Scanning
When you change the size of a connection, you must download to the
device for the change to take effect. When downloading to a device
that a master is currently scanning, you must:
1. Access the DeviceNet scanner’s scanlist to remove the device
from the scanlist.
2. Put the master in Idle mode. (This may mean turning a
processor’s keyswitch to Program.)
3. Access the device’s parameters to change the size of the
connection.
4. Download to the device.
5. Add the device to the scanlist and click Apply.
6. Click the Edit I/O Parameters button and verify that the Rx and
Tx size corresponds to the new size.
7. Put the master in Run mode for normal operation.