Rockwell Automation DeviceLogix System User Manual User Manual

Page 194

Advertising
background image

194

Publication RA-UM003B-EN-P - February 2010

Appendix B RSNetWorx for DeviceNet Software and the DeviceLogix Editors

To the change the network status override:

1. Click the current value of the Network Status Override

parameter.

The field turns into a drop-down list box.

2. Click the arrow to display the values.

3. Click the desired value.

4. Click Apply to save the new value without closing the window.

Or click OK to save the new value and to close the window.

Download to a Device That Is Scanning

When you change the size of a connection, you must download to the
device for the change to take effect. When downloading to a device
that a master is currently scanning, you must:

1. Access the DeviceNet scanner’s scanlist to remove the device

from the scanlist.

2. Put the master in Idle mode. (This may mean turning a

processor’s keyswitch to Program.)

3. Access the device’s parameters to change the size of the

connection.

4. Download to the device.

5. Add the device to the scanlist and click Apply.

6. Click the Edit I/O Parameters button and verify that the Rx and

Tx size corresponds to the new size.

7. Put the master in Run mode for normal operation.