Launch the DeviceLogix Editor

After you configure the properties for your DeviceLogix-enabled
device, you can launch the DeviceLogix Editor. You see an additional
tab in the device properties dialog box for all DeviceLogix-enabled
devices. This tab is labeled DeviceLogix. This tab provides access to
the start-up window for the DeviceLogix Editor. You have the option
to fill in your name, a revision number, and a description of your
configuration (all optional fields). The Last Saved box updates every
time you save within RSNetWorx for DeviceNet software.

IMPORTANT

If you are on line and you click on either the Parameters or the
DeviceLogix tab, you may be prompted to upload or download
the device. When you are on line, the dialog checks the
configuration in the device and compares it to the current
configuration. If the configurations are not the same, you must
upload from or download to the device to make the
configurations the same before you can make changes. If you
need to make changes without uploading or downloading, you
can exit the dialog box, go off line and re-enter the dialog box
to make the desired changes.