Rockwell Automation DeviceLogix System User Manual User Manual

Page 30

Advertising
background image

30

Publication RA-UM003B-EN-P - February 2010

Chapter 2 Navigate the Function Block Editor Interface

Zero-crossing is deadband control that lets the function block
use the error for computational purposes as the process variable
crosses into the deadband until the process variable crosses the
setpoint. Once the process variable crosses the setpoint (error
crosses zero and changes sign), and as long as the process
variable remains in the deadband, the function block considers
the error value to be zero. The deadband has the same scaled
units as the setpoint.

Output Limit

An output limit (percent of output) can be set on the control
output. When the function block detects that the output has
reached a limit, the PID function block automatically avoids
reset windup by preventing the integral term from accumulating
whenever the CV output reaches its maximum or minimum
values. The accumulated integral term remains frozen until the
CV output drops below its maximum limit or rises above its
minimum limit. Normal integral accumulation automatically
resumes.

Scaling Parameters

Scaling parameters allow you to set the output scale.

Parameter

Type

Default

Description

PV Max

REAL

0.0

Maximum value for the unscaled Process
Variable (PV).

This parameter cannot be configured when the
DeviceLogix logic is in the Run mode.

PV Min

REAL

0.0

Minimum value for the unscaled Process
Variable (PV).

This parameter cannot be configured when the
DeviceLogix logic is in the Run mode.

EU Max

REAL

0.0

Maximum engineering unit for the Process
Variable (PV).

This parameter cannot be configured when the
DeviceLogix logic is in the Run mode.

EU Min

REAL

0.0

Minimum engineering unit for the Process
Variable (PV).

This parameter cannot be configured when the
DeviceLogix logic is in the Run mode.

CV Max (at 100%)

REAL

0.0

Maximum value for the unscaled Control
Variable (CV).

This parameter cannot be configured when the
DeviceLogix logic is in the Run mode.

Advertising