Rockwell Automation WebPak 3000 User Guide User Manual
Page 16

2-6
WebPak 3000 OIM User Guide
2.2.1 Drive Status Indicators
The indicators on the right of the display allow you to check the status of the drive. In
figure 2.2, the Interlocks OK and Drive Ready indicators are shown on. The indicators
are described in table 2.3.
Table 2.3 – Drive Status Indicators
Indicator
State
Description
Fault
On
At least one fault has occurred. See chapter 7 for fault information.
Off
There are no faults.
Alarm
On
At least one alarm has occurred. See chapter 7 for alarm information.
Off
There are no alarms.
Interlocks OK
On
The coast/DB contact and all customer interlocks (Regulator board terminal 9) are
closed. See the hardware manual for more information.
Off
One or more customer interlocks or the coast/DB contact is open.
Drive Ready
On
Drive is ready to run or jog. All customer interlocks are closed, the coast/DB
contact is closed, and there are no faults.
Off
Drive is not ready. See chapter 7 for diagnostics information.
Running
On
The contactor is closed and the motor armature is energized in either run or jog
mode. The drive is running.
Off
The contactor is open and the drive is not running.
Current Limit
Torque Limit
On
Drive is operating at the maximum allowable current or torque.
Off
Drive is not at the maximum allowable current or torque.