Basics of Configuring the Drive Using the OIM

4-7

Step 6. Press

to accept the changed value and go to step 7.

Step 7. Press

to return to the list of parameters.

Step 8. To save the changes to the parameters, you must perform a memory save.

See section 4.4, “Saving and Restoring Parameter Values”.

Step 9. Record changes to parameter values in the software manual.

4.2.6 Parameter Values That Cannot Be Changed

In some cases, you cannot change parameter values. If this is the case, an error
message is displayed when you try to select the parameter. The situations in which
you cannot change parameter values are:

When the drive is running and the parameter you are changing is configurable.
Configurable parameters cannot be changed while the drive is running or jogging.
Stop the drive to change the parameter.

When password or hardware program protection is enabled. See section 4.3, “Using
a Password to Protect Configuration”, for information on password program
protection. See the hardware manual for hardware program protection.

If the parameter is an output. Output parameters can only be displayed.

4.3

Using a Password to Protect Configuration

To prevent changes to parameters from the

OIM

, you can use software or hardware

program protection. Program protection does not affect keypad control, the contrast
and language configuration, the fault and alarm options, or monitor mode. It has no
effect on changes made through the serial port.

Hardware-based program protection is enabled by a jumper setting and is described
in the hardware manual. Software-based program protection is enabled through the

PASSWORD

parameter and is described later in this section.

Important: Hardware program protection takes precedence over software program

protection. If hardware program protection is set to

DISABLE

, the

PASSWORD

parameter is ignored.

When password program protection is enabled and you select a parameter, the
message “Do you wish to enter the password to

DISABLE

program protection”

is

displayed. You must enter the factory-set password to change the parameter. This
disables software program protection. To re-enable software program protection,
repeat the following procedure.

If you do not enter the correct password when you try to change a parameter, the
message “

PROGRAM

ERROR

!

PASSWORD

PROTECTION

IS

ENABLED

” is displayed.

!

ATTENTION: It is the user’s responsibility to distribute the security
password. Reliance Electric is not responsible for unauthorized access
violations within the user’s organization. Failure to observe this
precaution could result in bodily injury.