WebPak 3000 OIM User Guide

REVERSE

DISABLE

(P.015)

Enables or disables
the speed reference
from dropping below
zero.

Parameter Range:

OFF

ON

Default Setting:

OFF

Parameter Type:

Configurable

ON

: The speed reference is prevented from dropping below zero.

OFF

: The speed reference can drop below zero and the drive can operate in the

opposite direction.

FEEDBACK

SELECT

(P.200)

Selects the type of
feedback signal used
for the speed/voltage
loop.

Parameter Range:

ARMATURE

VOLT

DC

TACH

ENCODER

Default Setting:

ARMATURE

VOLT

Parameter Type:

Configurable

ARMATURE

VOLT

: The drive reads the internal armature voltage and scales it with the

MOTOR

RATED

ARM

VOLTS

(P.009),

ARM

VOLTAGE

GAIN

ADJ

(P.204), and

ARM

VOLTAGE

ZERO

ADJ

(P.205) parameter values. These values are summed to produce the

armature voltage signal.

DC

TACH

: The tachometer is connected to analog input terminals (+

HI

) 21 or (+

LO

)

22, and (-) 23 on the Regulator board terminal strip. The choice for (+

HI

) and (+

LO

)

is determined by tables associated with the settings of

J

11

ANLG

TACH

VLT

SCL

(P.792) and

J

14

ANLG

TACH

VLT

RNG

(P.793).

ENCODER

: Instruction sheet D2-3302 should be used to apply and configure the

encoder. This instruction sheet covers the optional encoder interface kit that must
be added to support this feedback option. Since the WebPak 3000 drive standard
design is a regenerative power bridge, a dual-channel differential-output encoder is
required. encoder can only be selected if the Pulse Encoder (Tachometer) kit is
installed.

!

ATTENTION: The incorrect configuration of

FEEDBACK

SELECT

(P.200)

can cause an overspeed condition. This parameter must be configured
by a qualified person who understands the significance of setting it
accurately. Failure to observe this precaution could result in bodily injury.