7 resetting the clock – Rockwell Automation WebPak 3000  User Guide User Manual

Page 67

Advertising
background image

Troubleshooting the Drive Using the OIM

7-9

You must remove the

OIM

assembly from the drive to replace the circuit board. See

section 7.6.1, “Preparing to Replace the OIM”, and section 7.6.2, “Accessing the OIM
and Disconnecting It from the Regulator Board”, for instructions.

To replace the circuit board:

Step 1. Place the

OIM

assembly face down on a surface that will not scratch the

OIM

front panel.

Step 2. Remove the four screws holding the circuit board to the mounting plate.

Step 3. Lift the circuit board from the standoffs. Remove the washers if they detach

from the screws.

Step 4. Place the new circuit board on the standoffs. Make sure the 20-pin

connector is properly aligned with the matching header on the Regulator
board (J3).

Step 5. Tighten the four screws holding the board to the mounting plate.

Step 6. Connect the ground wire from the drive to the ground terminal on the

OIM

mounting plate.

Step 7. Replace the four screws securing the

OIM

assembly to the drive.

Step 8. Connect the communication cable from the

OIM

assembly to J9 on the

Regulator board.

Step 9. Replace the drive front cover and tighten the screws, securing it to the drive

enclosure.

7.6.4 Replacing the Entire OIM Assembly

Follow this procedure if you are replacing the entire

OIM

assembly. If you are replacing

the circuit board, see section 7.6.3, “Replacing the OIM Circuit Board Only”.

You must remove the old

OIM

assembly from the drive before replacing it. See

section 7.6.1, “Preparing to Replace the OIM”, and section 7.6.2, “Accessing the OIM
and Disconnecting It from the Regulator Board”, for instructions.

To replace the

OIM

:

Step 1. Connect the ground wire from the drive to the ground terminal on the

OIM

mounting plate. If you are replacing an older version of the

OIM

, you might

need to use the hardware from the old unit.

Step 2. Replace the four screws securing the

OIM

assembly to the drive.

Step 3. Connect the communication cable from the

OIM

assembly to J9 on the

Regulator board, making sure that it locks into place.

Step 4. Replace the drive front cover and tighten the screws, securing it to the drive

enclosure.

7.7

Resetting the Clock

The elapsed time clock on the drive displays the day and time since the last power
cycle or clock reset. The time is based on an internal 248-day counter.

Advertising