Using Quick Start

5-5

Step 4. Set

to

KEYPAD

or

TERMBLK

. See section 6.2 for instructions.

Step 5. Clear any faults from the fault log. See chapter 7 for information.

If you do not do these steps, you will get an error message when you try to start self-tuning.

5.4.2 Performing the Self-Tuning Procedure

Before self-tuning, complete the steps in section 5.4.1.

To perform self-tuning:

Step 1. Configure the self-tune parameters listed here. For descriptions of these

parameters, see section 5.4.5, or see the software manual.

SELF

TUNE

BRIDGE

(P.220)

SELF

TUNE

STABILITY

(P.219)

Step 2. Access the Self Tuning menu from either the menus or from Quick Start.

From the menus:

a. Select Speed/Voltage Loop (

SPD

). Press

.

b. Select Speed/Voltage Loop (

SPD

) Tuning. Press

.

c. Select Self Tuning.

or

a. Select Current Minor Loop (

CML

). Press

.

b. Select

CML

Tuning. Press

.

c. Select Self Tuning.

From Quick Start:

The self-tuning menu is displayed after you configure the other Quick Start
parameters.

Step 3. If

FEEDBACK

SELECT

(P.200) is set to

ARMATURE

VOLT

, go to step 4. If

FEEDBACK

SELECT

(P.200) is not set to

ARMATURE

VOLT

, select one of these

types of self-tuning. Press

.

CML

and

SPEED

Loop: Self-tunes the current minor loop and then the

speed loop.

CML

only: Self-tunes only the current minor loop.

SPEED

only: Self-tunes only the speed control loop. The current minor loop

should have been tuned before tuning only the speed loop.

Step 4. The message in figure 5.4 is displayed. To start self-tuning, press

.