P.207), P.001) – Rockwell Automation WebPak 3000 User Guide User Manual
Page 47
 
Using Quick Start
5-11
ANLG
TACH
VOLTS
/1000 (P.203)
Specifies the scaling 
of the analog 
tachometer (as it 
appears on the 
tachometer 
nameplate) in volts 
per 1000 
RPM
.
Parameter Range:*
18.0 to 200.0
VOLTS
/1000
RPM
Default Setting:
18.0
VOLTS
/1000
RPM
Parameter Type:
Configurable
*Depending on the setting of
GEAR
IN
SPEED
(P.011), the high limit might be less
than 200.0 to prevent the tachometer voltage from exceeding 250V.
This parameter is only available if
FEEDBACK
SELECT
(P.200) is set to
DC
TACH
.
ENCODER
PPR
(P.207)
Pulse encoder pulses 
per revolution (
PPR
)
from the pulse 
encoder nameplate.
Parameter Range:
18 to 5000
PPR
Default Setting:
18
PPR
Parameter Type:
Configurable
Only available if
FEEDBACK
SELECT
is set to
ENCODER
.
ACCELERATION
TIME
(P.001)
Sets the minimum 
time that the selected 
speed reference can 
change from zero to 
GEAR
IN
SPEED
(P.011).
Parameter Range:
0.1 to 300.0
SECONDS
Default Setting:
5.0
SECONDS
Parameter Type:
Tunable
If
TRIM
MODE
SELECT
(P.110) is set to
PROPORTIONAL
, the actual time to accelerate
might be modified by
DRAW
PERCENTAGE
OUT
(P.196).
!
ATTENTION: The incorrect configuration of
ENCODER
PPR
(P.207) can
cause an overspeed condition. This parameter must be configured by a 
qualified person who understands the significance of configuring it 
accurately. Failure to observe this prcaution could result in bodily injury.
!
ATTENTION: The incorrect configuration of
ANLG
TACH
VOLTS
/1000
(P.203) can cause an overspeed condition. This parameter must be 
configured by a qualified person who understands the significance of 
setting it accurately. Failure to observe this precaution could result in 
bodily injury.