Using Quick Start

5-11

ANLG

TACH

VOLTS

/1000 (P.203)

Specifies the scaling
of the analog
tachometer (as it
appears on the
tachometer
nameplate) in volts
per 1000

RPM

.

Parameter Range:*

18.0 to 200.0

VOLTS

/1000

RPM

Default Setting:

18.0

VOLTS

/1000

RPM

Parameter Type:

Configurable

*Depending on the setting of

GEAR

IN

SPEED

(P.011), the high limit might be less

than 200.0 to prevent the tachometer voltage from exceeding 250V.

This parameter is only available if

FEEDBACK

SELECT

(P.200) is set to

DC

TACH

.

ENCODER

PPR

(P.207)

Pulse encoder pulses
per revolution (

PPR

)

from the pulse
encoder nameplate.

Parameter Range:

18 to 5000

PPR

Default Setting:

18

PPR

Parameter Type:

Configurable

Only available if

FEEDBACK

SELECT

is set to

ENCODER

.

ACCELERATION

TIME

(P.001)

Sets the minimum
time that the selected
speed reference can
change from zero to

GEAR

IN

SPEED

(P.011).

Parameter Range:

0.1 to 300.0

SECONDS

Default Setting:

5.0

SECONDS

Parameter Type:

Tunable

If

TRIM

MODE

SELECT

(P.110) is set to

PROPORTIONAL

, the actual time to accelerate

might be modified by

DRAW

PERCENTAGE

OUT

(P.196).

!

ATTENTION: The incorrect configuration of

ENCODER

PPR

(P.207) can

cause an overspeed condition. This parameter must be configured by a
qualified person who understands the significance of configuring it
accurately. Failure to observe this prcaution could result in bodily injury.

!

ATTENTION: The incorrect configuration of

ANLG

TACH

VOLTS

/1000

(P.203) can cause an overspeed condition. This parameter must be
configured by a qualified person who understands the significance of
setting it accurately. Failure to observe this precaution could result in
bodily injury.