6 replacing the oim – Rockwell Automation WebPak 3000  User Guide User Manual

Page 66

Advertising
background image

7-8

WebPak 3000 OIM User Guide

7.6

Replacing the OIM

The WebPak 3000 Operator Interface Module kit (M/N 925WK0101) is used to replace
the drive’s built-in keypad and display. If necessary, the entire

OIM

(P/N 807313-2R) or

the

OIM

circuit board (P/N 179233) can be replaced using this procedure.

7.6.1 Preparing to Replace the OIM

Before replacing the

OIM

, disconnect power from the drive.

You will need the following tools:

#1 Phillips screwdriver

#2 Phillips screwdriver

M7 Hex wrench or socket wrench

7.6.2 Accessing the OIM and Disconnecting It from the Regulator Board

These steps are required for both

OIM

circuit board and complete

OIM

replacement.

Important: Unless otherwise indicated, keep all hardware for the replacement

procedure.

Step 1. Loosen the screws that secure the front cover to the drive.

Step 2. Remove the front cover.

Step 3. Disconnect the communication cable from J9 on the Regulator board by

pressing down the locking clip and pulling the cable out.

Step 4. Remove the four screws holding the

OIM

assembly to the drive enclosure.

Step 5. Pull the

OIM

assembly away from the drive so you can access the ground

wire on the upper right corner of the

OIM

mounting plate. Slide the ground

wire off its connection.

Important: Ground wires on older versions of the

OIM

are fastened by a nut. If you are

replacing an older version, keep the hardware so you can re-attach the
ground wire.

7.6.3 Replacing the OIM Circuit Board Only

Follow this procedure if you are replacing only the circuit board. If you are replacing
the entire

OIM

assembly, see section 7.6.4, “Replacing the Entire OIM Assembly”.

!

ATTENTION: Only qualified electrical personnel familiar with the
construction and operation of this equipment and the hazards involved
should install, adjust, operate, or service this equipment. Read and
understand this section in its entirety before proceeding. Failure to
observe this precaution could result in severe bodily injury or loss of life.

ATTENTION: Do not install or remove the

OIM

with power applied to the

drive. Disconnect and lockout incoming power before attempting
installation or removal. Failure to observe this precaution could result in
severe bodily injury or loss of life.

Advertising