Rockwell Automation WebPak 3000  User Guide User Manual

Page 57

Advertising
background image

Using the OIM to Monitor and Control the Drive

6-5

To Jog the Drive:

Press

to jog the motor. The drive ramps up to the reference in the

time set by

JOG

ACCEL

/

DECEL

TIME

(P.013). The motor runs as long as

is held down.

When

is released, the motor ramps to stop in the time set by

JOG

ACCEL

/

DECEL

TIME

(P.013).

6.3.2 Stopping the Drive

When the drive is running, pressing

stops the drive in the manner selected by

STOP

MODE

SELECT

. When the

OIM

is connected and communicating with the drive,

is always active, regardless of the setting of

.

!

ATTENTION: The user must provide an external, hardwired emergency
stop circuit outside of the drive circuitry. This circuit must disable the
system in case of improper operation. Uncontrolled machine operation
can result if this procedure is not followed. Failure to observe this
precaution could result in bodily injury.