5-12

WebPak 3000 OIM User Guide

DECELERATION

TIME

(P.002)

Sets the minimum
time in which the
selected speed
reference can change
from

GEAR

IN

SPEED

(P.011) to zero.

Parameter Range:

0.1 to 300.0

SECONDS

Default Setting:

5.0

SECONDS

Parameter Type:

Tunable

If

TRIM

MODE

SELECT

(P.110) is set to

PROPORTIONAL

, the actual time to decelerate

might be modified by

DRAW

PERCENTAGE

OUT

(P.196).

MINIMUM

SPEED

(P.003)

Selects the minimum
speed of the drive
when running. It is
typically greater than
zero.

Parameter Range:

0 to

MAXIMUM

SPEED

(

RPM

or user-defined units)

Default Setting:

0

RPM

Parameter Type:

Tunable

If

MINIMUM

SPEED

is less than 10% of

MAXIMUM

SPEED

(P.004), an alarm is

generated.

!

ATTENTION: This drive can operate at and maintain zero speed when

MINIMUM

SPEED

(P.003) is set to zero. The user is responsible for assuring

safe conditions for operating personnel by providing suitable guards,
audible or visual alarms, or other devices to indicate that the drive is
operating at or near zero speed. Failure to observe this precaution could
result in severe bodily injury or loss of life.

ATTENTION:

MINIMUM

SPEED

is a tunable parameter and could affect

speed if it is adjusted while the drive is running. Failure to observe this
precaution could result in severe bodily injury or loss of life.