Basics of Configuring the Drive Using the OIM

4-9

4.4

Saving and Restoring Parameter Values

Through the

OIM

, you can save parameter values, restore parameter values from a

previous save, or restore default parameter values.

Memory Save

You must use Memory Save to save changes to parameter values and the language
setting through a power cycle. Any values that are not saved revert to the previous
value on power cycle.

Important: Memory Save does not save the

PASSWORD

parameter setting. To save

the

PASSWORD

, you must use the WebPak CS software.

Memory Restore

Restores the parameter values and monitor mode configuration from the last Memory
Save. Use Memory Restore if changes were made to the

OIM

that you do not want to

keep. If a Memory Save has never been performed, the factory defaults are restored.

Restore Defaults

Restores parameter values and monitor mode to the configuration set by the factory.

Important: After performing Restore Defaults, you should configure the parameters in

the Quick Start menu and perform the self-tuning procedure, described in
chapter 5.

4.4.1 Using Memory Operations to Save and Restore Parameter Values

To save, restore, or restore defaults:

Step 1. Press

until the

indicator reads

PROGRAM

and “WebPak 3000

Main Menu” is displayed at the top of the screen.

Step 2. Select Operator Interface. Press

.

Step 3. Select Memory Operations. Press

. The menu shown in figure 4.11

is displayed.

Figure 4.11 – Memory Operations Screen