5-2

WebPak 3000 OIM User Guide

The exit options are:

Return to previous step: Returns to the previous parameter. After you accept that
parameter value, Quick Start resumes from that parameter. To go back several

parameters, you can press

and select “Return to previous step” as many

times as needed.

Exit Quick Start using changes: Exits Quick Start and accepts any changes. You
must use Memory Save to save the changes through a power cycle. See
section 4.4, “Saving and Restoring Parameter Values”, for more information.

Exit Q.S. without using changes: Exits Quick Start. Changes are ignored.

To leave the exit menu without selecting any of the options: Press

. You return

to the Quick Start parameter entry screen.

5.3

Configuring the Drive Using Quick Start

Important: If program protection is enabled, you cannot change Quick Start

parameters. See section 4.3, “Using a Password to Protect
Configuration”, to disable password program protection, or the hardware
manual for removing hardware program protection.

Before performing Quick Start, you might need to configure the AC line parameters,

NOMINAL

AC

LINE

FREQ

(P.306) or

NOMINAL

AC

LINE

VOLTS

(P.307), for your application.

Generally, you only need to configure these parameters if the default values for these
parameters are incorrect for your application (typically indicated by the alarm

AC

LINE

VOLTAGE

HIGH

or

AC

LINE

VOLTAGE

LOW

). If you need to adjust these parameters, you

should change them before performing Quick Start. See the software manual for
descriptions of these parameters.

To use Quick Start:

Step 1. Make sure the drive is stopped (the Running status indicator is off).

Step 2. Press

and select

KEYPAD

. Press

. (See section 6.2 for more

detail on selecting a control source.)

Step 3. Press

until its key indicator reads

PROGRAM

.

Step 4. Move the cursor ( ) to the Quick Start menu. Press

.

Quick Start begins. The first parameter is displayed, as shown in figure 5.2.

!

ATTENTION: Only qualified electrical personnel familiar with the
construction and operation of this equipment and the hazards involved
should install, adjust, operate, or service this equipment. Read and
understand this section in its entirety before proceeding. Failure to
observe this precaution could result in severe bodily injury or loss of life.

ATTENTION: Incorrect values for some of the parameters in Quick Start
can cause the drive to operate improperly. Verify that the values of these
parameters are appropriate for your application. Failure to observe these
precautions could result in bodily injury.