P.510) – Rockwell Automation WebPak 3000  User Guide User Manual

Page 51

Advertising
background image

Using Quick Start

5-15

MOTOR

HOT

FLD

AMPS

(P.510)

Sets the motor
nameplate value of
the rated hot field
amps. This input is
the basis of field
current scaling.

Parameter Range:

0.11 to

INSTALLED

SUPPLY

RATING

(4.00, 10.00, or

20.00

AMPS

)

Default Setting:

0.01

AMPS

Parameter Type:

Configurable

If the factory defaults are restored, or if a valid value has not yet been entered for
this parameter, the DC field voltage is fixed at 150 V on a 230VAC line, or at 300V
on a 460VAC line.

!

ATTENTION: The incorrect configuration of

MOTOR

HOT

FLD

AMPS

(P.510)

can cause a motor overvoltage condition. Configure

MOTOR

HOT

FLD

AMPS

to the motor’s nameplate value. Failure to observe this precaution can
result in bodily injury and damage to the equipment.