3.1.3 Verifying the Site Provides for Recommended Air Flow Clearances
Be sure there is adequate clearance for air circulation around the drive. For best air
movement, do not mount GV3000/SE Bookshelf drives directly above each other.
Note that no devices are to be mounted behind the drive. This area must be kept clear
of all control and power wiring.
When mounting the drive within a cabinet, maintain the minimum clearances shown in
table 3.4 to allow adequate air circulation around and through the drive.
Table 3.3 – Dimensions and Weight for 43 Amp Drives
U.S.
Model
Number
European
Stock
Number
Physical Dimensions in mm (in)
Weight
Width Dim A
mm (in)
Height Dim B
mm (in)
Width Dim C
mm (in)
Mounting
Height Dim D
mm (in)
Depth Dim E
mm (in)
kg
lb
430ER40xx
430ET40xx
896.11.12
896.11.32
214 (8.42 )
374 (14.72)
150 (5.90)
422 (16.61)
200 (7.87)
16.5
36
Figure 3.2 – Dimensions for 43 Amp Drives
A
Ø 14
E
C
B
D
Front View
Side View
Table 3.4 – Recommended Air Flow Clearances
Minimum Clearance
Above and below the Bookshelf drive
100 mm
4 in
Between the Bookshelf drive and side cabinet
walls
20 mm
.75 in
Between Bookshelf drives
5 mm
.25 in
Between other larger drives or heat-producing
devices
40 mm
1.5 in