7-10

GV3000/SE AC Bookshelf Drive Hardware Reference, Version 6.06

Table 7.6 - Wiring Signal and Control I/O to the Regulator Board Terminal Strip (Continued)

Terminal

Number

Description

Parameters/Wiring Connections

Wiring an Additional Ramp Input

18

Digital Input 7

(Default - Ramp 1/Ramp 2)

Digital input 7 is control function programmable through

parameter P.007. The following parameters must be set:

P.000: Control Source

P.001: Accel Time 1 (Ramp 1)

P.002: Decel Time 1 (Ramp 1)

P.006: Second Menu Password

P.007: Terminal Strip Digital Inputs Configure (Selects and

assigns a control function to digital inputs 6 to 8)

P.008: Terminal Strip Speed Reference Source (Analog

Motor Operated Potentiometer (MOP), or Preset

Speeds)

P.017: Accel Time 2 (Ramp 2)

P.018: Decel Time 2 (Ramp 2)

Note that based on the settings of parameters P.000, P.007,

P.008, and r.030 if an RMI board is used, the following

parameters can affect digital input 7:

P.023: MOP Accel/Decel Time

P.024: MOP Reset Configuration

P.031 to P.038: Preset Speeds 1-8

Refer to the GV3000/SE Bookshelf Drive Software Start-Up

and Reference manual for additional information.

Terminal 18 On = Ramp 2

Diagram shows factory setting.