Rockwell Automation GV3000/SE AC Bookshelf Drive Hardware Ref, Installation, and Troubleshooting User Manual
Page 60

7-10
GV3000/SE AC Bookshelf Drive Hardware Reference, Version 6.06
Table 7.6 - Wiring Signal and Control I/O to the Regulator Board Terminal Strip (Continued)
Terminal
Number
Description
Parameters/Wiring Connections
Wiring an Additional Ramp Input
18
Digital Input 7
(Default - Ramp 1/Ramp 2)
Digital input 7 is control function programmable through
parameter P.007. The following parameters must be set:
•
P.000: Control Source
•
P.001: Accel Time 1 (Ramp 1)
•
P.002: Decel Time 1 (Ramp 1)
•
P.006: Second Menu Password
•
P.007: Terminal Strip Digital Inputs Configure (Selects and
assigns a control function to digital inputs 6 to 8)
•
P.008: Terminal Strip Speed Reference Source (Analog
Motor Operated Potentiometer (MOP), or Preset
Speeds)
•
P.017: Accel Time 2 (Ramp 2)
•
P.018: Decel Time 2 (Ramp 2)
Note that based on the settings of parameters P.000, P.007,
P.008, and r.030 if an RMI board is used, the following
parameters can affect digital input 7:
•
P.023: MOP Accel/Decel Time
•
P.024: MOP Reset Configuration
•
P.031 to P.038: Preset Speeds 1-8
Refer to the GV3000/SE Bookshelf Drive Software Start-Up
and Reference manual for additional information.
Terminal 18 On = Ramp 2
Diagram shows factory setting.