Rockwell Automation GV3000/SE AC Bookshelf Drive Hardware Ref, Installation, and Troubleshooting User Manual

Page 37

Advertising
background image

Planning Before Installing

3-9

3.2.4 Meeting Encoder Specifications (FVC Regulation Only)

GV3000/SE drives set up for FVC regulation require an encoder for closed-loop

operation. Refer to table A.5 for specifications. Drives set up for V/Hz or SVC

regulation do not require an encoder for feedback.

3.2.4.1 Encoder Wiring Guidelines

Encoder connections are considered signal level wiring and, therefore, must be run

separate from control and power wiring. Reliance Electric recommends 18 AWG

unshielded twisted pair wires with 2-3 twists per inch for applications to a maximum

distance of 303 meters (1000 feet). The recommended Reliance Electric part number

is 417900-207CG; 18 AWG, 6 conductor (3 twisted pairs).

3.2.5 Verifying Power Module Output Current Rating Is Greater Than

Motor Full Load Amps

Verify that the GV3000/SE output current rating is greater than the motor’s full load

current (amps). Table 2.1 lists the output current values.

300ER40xx

896.09.11

No

38 A

50 A

50 A

300ET40xx

896.09.31

Yes

32 A

430ER40xx

896.11.12

No

53 A

63 A

63 A

430ET40xx

896.11.32

Yes

47 A

1

AC line input current (RMS) is dependent on total line impedance.

2

Recommended type of external input fuse:

AC line input: Branch circuit protection fuse, e.g., IEC 269-1/gG, EN 60269-1, VDE 0636/gL, UL Class

J, or equivalent.

DC bus input: Semiconductor protection fuse, 660 V or 750 V, superfast, e.g., A70P500, VDE 0636/aR,

or equivalent.

Table 3.10 – AC Input Fuse Selection Values (Continued)

U.S.

Model

Number

European

Stock

Number

Choke

AC Input

Current

1

External Fuse

2

Nominal

Maximum