background image

10-6

GV3000/SE AC Bookshelf Drive Hardware Reference, Version 6.06

IGBT

No.

Meter

Connection

(+) (-)

Component is OK if

resistance (R) is:

Component is defective if:

V6

47*

W(T3)

0.3 < R < 8K ohm

Continuity (short circuit) or

open when the meter is

connected with reversed

polarity

V5

47*

V(T2)

V4

47*

U(T1)

V3

W(T3)

45*

V2

V(T2)

45*

V1

U(T1)

45*

*If the optional terminals 45 and 47 are not fitted (e.g., on drives with built-in chopper option), remove

cover and connect the meter to the measuring points according to the procedure in section 10.3.