Planning Before Installing

3-7

Standard reactors can be used on GV3000/SE drives with carrier frequency settings up to 8 kHz.
All reactors listed are UL-recognized (UL-506 File #E53094) and CSA certified (CSA File # LR29753).

Figure 3.3 – How to Calculate Motor Lead Lengths

GV3000/SE

Drive

Motor

38 m (125’)

38 m (125’)

15 m (50’)

61 m (200’)

61 m (200’)

8 m (25’)

8 m (25’)

76 m (250’)

Motor

Motor

Motor

Motor

Motor

Motor

GV3000/SE

Drive

GV3000/SE

Drive

GV3000/SE

Drive

This example shows how to measure various motor configurations when the maximum motor lead length is 76 m (250 ft). Note that drives using

vector regulation can be connected to only one motor at a time.

Table 3.8 – Recommended Motor Lead Lengths for Reliance Inverter Duty Motors

Maximum Lead Length in Feet with

460 VAC Motor

GV3000/SE

Amp Rating

Filter Type

Carrier Frequency

2 kHz

4 kHz

8 kHz

3.1 to 3.8

None

500

500

500

5.5 to 8.5

500

500

500

12.6 to 15

750

500

500

24 to 43

800

500

500

3.1 to 3.8

A 5% reactor/filter

at the drive.

1000

1000

1000

5.5 to 8.5

1000

1000

1000

12.6 to 15

1000

1000

1000

24 to 43

1000

1000

1000

Table 3.9 – Compatible Reactors

GV3000/SE

Amp Rating

480 Volt

5% Reactor

3.1

RL-00202

3.8

RL-00403

5.5

RL-00403

8.5

RL-00803

12.6

RL-01203

15

RL-01803

24

RL-02503

30

RL-03503

43

RL-04503

Advertising