Wiring the Regulator Board Terminal Strip and the Output Relay Terminal Strip

7-5

The required external hardwired emergency stop must be either a category 0 or 1

stop, depending on the user’s risk assessment of the associated machinery. In order

to fully comply with machinery safety standard EN60204-1:1992, part 9.2.5.4, at least

one of the two stop methods must be a category 0 stop. Refer to Appendix B for more

information.

7.2 Wiring the Encoder Feedback Device

(FVC Regulation Only)

If the GV3000/SE drive is programmed to provide FVC regulation, an encoder must be

installed on the motor. Drives using V/Hz or SVC regulation do not require the use of

an encoder feedback device. The encoder connects to terminals 4 through 9 of the

Regulator board terminal strip as shown in table 7.6:

Use the following procedure to connect an encoder to the Regulator board terminal

strip:
Step 1. Connect the encoder’s wires to terminals 4 through 9 of the terminal strip.

See figure 7.3. Refer to section 3.2.4.1 for encoder wiring guidelines.

Step 2. Set the following parameters to establish the maximum motor speed:

P.004: Maximum Speed

U.001: Encoder PPR

U.002: Motor Poles

U.003: Motor Nameplate Base Frequency

U.005: Motor Nameplate RPM

U.017: Motor Top Speed

Refer to the GV3000/SE Bookshelf Drive Software Start-Up and Reference manual for

parameter descriptions.

Table 7.6 – Encoder Connections

Terminal

Encoder Connection

4

Encoder Supply +15 VDC (250 mA capacity)

5

Encoder Phase A Differential Input

6

Encoder Phase A Not Differential Input

7

Encoder Phase B Differential Input

8

Encoder Phase B Not Differential Input

9

Encoder/Regulator Common