Wiring Optional User-Supplied Braking Resistors

8-1

C

HAPTER

8

Wiring Optional User-Supplied

Braking Resistors

This chapter describes how to select and wire optional user-supplied braking
resistors.

8.1 Installation Guidelines

Use the following guidelines when installing braking resistors:

The cable length of the connection between the braking unit and the resistor must
not exceed 2.5 m (8 ft).

Provide ground connections as shown in figure 8.1.

The conductors should be twisted together and run separate from other conductors.

If the braking resistor is mounted in a separate enclosure, this must be metallic
conductive and the diameter of ventilation holes should not exceed 6 mm (.236 in).

Heat-resistant cables and cable sockets (minimum 90

°

C) must be used to connect

the braking resistor.

Wire rated at a minimum of least 600 volts for 460 VAC must be used. Refer to table
8.1 for cable cross-section specifications.

If the drive installation must be in compliance with the European community
electromagnetic compatibility standards, refer to Appendix C.

!

ATTENTION: The user is responsible for conforming with all applicable

local, national, and international codes. Failure to observe this precaution

could result in damage to, or destruction of, the equipment.

!

ATTENTION: It is important to use wire rated at 600 volts for 460 VAC

because this wiring may make contact with uninsulated 460 VAC

components. Failure to observe this precaution could result in damage

to, or destruction of, the equipment.