Wiring the Regulator Board Terminal Strip and the Output Relay Terminal Strip

7-13

Table 7.6 - Wiring Signal and Control I/O to the Regulator Board Terminal Strip (Continued)

Terminal

Number

Description

Parameters/Wiring Connections

Wiring the Reset Input

22

Digital Input 3

(Reset)

The following parameter must be set:

P.000: Control Source

Terminal 22 On = Reset

Wiring the Stop/Start Inputs

23

24

Digital Input 2

(Stop)

Digital Input 1

(Start)

The following parameter must be set:

P.000: Control Source

P.025: Stop Type

Terminal 23 Off = Stop

Terminal 24 On Transition = Start

25

24 VDC Isolated Common