Rockwell Automation GV3000/SE AC Bookshelf Drive Hardware Ref, Installation, and Troubleshooting User Manual

Page 58

Advertising
background image

7-8

GV3000/SE AC Bookshelf Drive Hardware Reference, Version 6.06

Table 7.6 - Wiring Signal and Control I/O to the Regulator Board Terminal Strip (Continued)

Terminal

Number

Description

Parameters/Wiring Connections

Wiring Analog Speed Reference Inputs

12

13

14

15

Isolated Reference

Voltage (+10 VDC)

Analog Speed/Torque

Reference Input Voltage

(+/- 10 VDC)

Analog Speed/Torque

Reference Input Current

(0-20 mA)

Isolated Speed/Torque

Reference Common

(Voltage/Current)

Related parameters:

P.000: Control Source

P.009: Terminal Strip Analog Input Offset

P.010: Terminal Strip Analog Input Gain

P.011: Terminal Strip Analog Input Configure

Refer to the GV3000/SE Bookshelf Drive Software Start-Up

and Reference manual for additional parameter information.
Jumper J4 must also be set. See figure 2.7.

Refer to Appendix G of the GV3000/SE Bookshelf Drive

Software Start-Up and Reference manual for more

information about the analog input.

Advertising