Wiring the Regulator Board Terminal Strip and the Output Relay Terminal Strip

7-9

Table 7.6 - Wiring Signal and Control I/O to the Regulator Board Terminal Strip (Continued)

Terminal

Number

Description

Parameters/Wiring Connections

Wiring a Remote/Local Input

16

+24 VDC Power Supply

Current limited for remote input logic use only.

17

Digital Input 8

(Default - Remote/Local)

Digital input 8 is control function programmable through

parameter P.007.

!

ATTENTION: If a maintained start contact is used when the control source = rE, switching

from local to remote from the terminal strip will cause power to be applied to the motor if

the remote start contact is closed. Stay clear of rotating machinery in this case. Failure to

observe this precaution could result in bodily injury.

The following parameters must be set:

P.000: Control Source (Only active when P.000 = rE)

P.006: Second Menu Password

P.007: Terminal Strip Digital Inputs Configure (Selects and

assigns a control function to digital inputs 6 to 8)

P.008: Terminal Strip Speed Reference Source

(Analog, Motor Operated Potentiometer (MOP), or

Preset Speeds)

Note that based on the settings of parameters P.000, P.007,

P.008, and r.030 if an RMI board is used, the following

parameters can affect digital input 8:

P.023: MOP Accel/Decel Time

P.024: MOP Reset Configuration

P.031 to P.038: Preset Speeds 1-8

Refer to the GV3000/SE Bookshelf Drive Software Start-Up

and Reference manual for additional information.

Terminal 17 On = Local Control

Diagram shows factory setting.