For drives not equipped with an AC Mains Filter, the maximum line distribution system

capacity is 315 KVA, three-phase with 10,000 amps symmetrical fault current capacity

with a line impedance of less than 5%.

5.2 Installing Fuses for Branch Circuit Protection

Install the required, user-supplied branch circuit protection fuses according to the

applicable local, national, and international codes (e.g., NEC/CEC). The fuses must

be installed in the line before the drive input terminals. See figure 5.1. Fuse value

selections are provided in table 3.10.

5.3 Installing a Required External/Separate Input

Disconnect

An input disconnect must be installed in the line before the drive input terminals in

accordance with local, national, and international codes (e.g., NEC/CEC). The

disconnect should be sized according to the in-rush current as well as any additional

loads the disconnect might supply. The trip rating for the inrush current (10-12 times

full load current) should be coordinated with that of the input isolation transformer, if

used. Refer to section 5.1 for additional information.

5.4 Installing Power Wiring from the AC Input Line to the

Drive’s Power Terminals

Use the following steps to connect AC input power to the drive:
Step 1. Wire the AC input power leads by routing them according to drive type. Refer

to figures 4.1, 4.2, or 4.3. Tables 3.5 and 3.6 contain the recommended

power wiring sizes.

Step 2. Connect the three-phase AC input power leads (three-wire 380-460 VAC) to

terminals L1, L2, L3.

Step 3. Tighten the AC input power terminals to 1.4 Nm (12 in-lb).

!

ATTENTION: Most codes require that upstream branch protection be

provided to protect input power wiring. Failure to observe this precaution

could result in severe bodily injury or loss of life.

!

ATTENTION: Do not route signal and control wiring with power wiring in

the same conduit. This can cause interference with drive operation.

Failure to observe this precaution could result in damage to, or

destruction of, the equipment.