7-12

GV3000/SE AC Bookshelf Drive Hardware Reference, Version 6.06

Table 7.6 - Wiring Signal and Control I/O to the Regulator Board Terminal Strip (Continued)

Terminal

Number

Description

Parameters/Wiring Connections

Wiring a Function Loss Input

20

Digital Input 5

(Function Loss)

The following parameters must be set:

P.026: Function Loss Response

A signal must be present at terminal 20 for the drive to be

able to start. See figures 7.1 and 7.2.
The drive is shipped from the factory with a jumper between

terminals 16 and 20 which provides the signal. The function

loss input should be in series with the drive’s external

interlocks. In this case, the jumper must be removed before

the connections are made.

Terminal 20 On = No Function Loss

Important: A maintained function loss switch should be

used if P.054 (Level Sense Start Enable) = ON

and P.026 (Function Loss Response) = 1.

Wiring a Run/Jog Input

21

Digital Input 4

(Run/Jog)

The following parameters must be set:

P.000: Control Source

P.020: Jog Speed Reference

P.021: Jog Ramp Accel Time

P.022: Jog Ramp Decel Time

Terminal 21 On = Jog Operation