Wiring the Regulator Board Terminal Strip and the Output Relay Terminal Strip

7-1

C

HAPTER

7

Wiring the Regulator Board

Terminal Strip and the

Output Relay Terminal Strip

This chapter describes how to wire the Regulator board terminal strip for stop,

encoder feedback, and remote control signals. It also describes how to wire the output

status relays on the output relay terminal strip.

The signals available through the Regulator board terminal strip are shown in tables

7.1 to 7.4 and figures 7.1 and 7.2. Table 7.6 provides additional information.

Note that when the Control Source parameter (P.000) is set to remote (rE), the drive

will be controlled by the signals connected to the terminal strip. Refer to the

GV3000/SE Bookshelf Drive Software Start-Up and Reference manual for more

information on how parameter P.000 is used to specify where the drive is controlled

from.

The signals available through the output relay terminal strip are shown in table 7.5.

Table 7.7 provides additional information.

Table 7.1 – Encoder Connections (Regulator Terminals 4-9)

Terminal #

Signal

4

+15 VDC

5

Phase A

6

Phase A Not

7

Phase B

8

Phase B Not

9

Regulator Common

Notes: An encoder feedback device must be installed if FVC regulation is used.

Table 7.2 – Analog Output Connections (Regulator Terminals 10 and 11)

Terminal #

Signal

10

Analog Meter Output

11

Analog Output Return

Notes: The output of this terminal is either 0-10 VDC or 4-20 mA as determined by the

setting of jumper J17 on the Regulator board. The analog output must also be

programmed via parameter P.012 for an indication of speed and direction or percent of

torque.