Chapter 1 Install a 1756 EtherNet/IP Communication Module

Set the Network IP Address with RSLinx Software

Follow these steps to use RSLinx software to set the communication module’s
IP address.

1. From the Communications menu, choose RSWho.

The RSWho dialog box appears.

2. Navigate to the Ethernet network.

3. Right-click the EtherNet/IP module and choose Module Configuration.

The Module Configuration dialog box appears.

4. Click the Port Configuration tab.

5. For Network Configuration Type, click Static to permanently assign this

configuration to the port.

6. Type this information in the appropriate fields:

IMPORTANT

If you select Dynamic, on a power cycle, the controller clears the
current IP configuration and resumes sending BOOTP requests.