Chapter 2, Install a 1768 ethernet/ip communication module, Chapter – Rockwell Automation 1756-Enxxx_Ewxxx EtherNet/IP Modules Installation Instructions User Manual

Page 35

Advertising
background image

Rockwell Automation Publication ENET-IN002F-EN-P - January 2014

35

Chapter

2

Install a 1768 EtherNet/IP Communication
Module

Topic

Page

Installation Summary

37

Set the Network IP Address

38

Install the Module

46

Wire the Module

48

Download the Add-on Profile

49

Download the Firmware

50

Apply Chassis Power and Check Status Indicators

51

Remove the Module

52

ATTENTION: Environment and Enclosure

This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined

in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating.

This equipment is not intended for use in residential environments and may not provide adequate protection to radio communication

services in such environments.

This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for those

specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from
accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or minimize the spread of flame,
complying with a flame spread rating of 5VA or be approved for the application if non-metallic. The interior of the enclosure must be
accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific
enclosure type ratings that are required to comply with certain product safety certifications.

In addition to this publication, see the following:

Industrial Automation Wiring and Grounding Guidelines, publication

1770-4.1

, for additional installation requirements

NEMA 250 and IEC 60529, as applicable, for explanations of the degrees of protection provided by enclosures

Advertising