Rockwell Automation Publication ENET-IN002F-EN-P - January 2014

33

Install a 1756 EtherNet/IP Communication Module Chapter 1

2. Check the power supply and module status indicators and alphanumeric

display to determine that the power supply and module are operating
properly.

The alphanumeric display should cycle through the following states:
TEST - PASS - OK - REV

x.x, where x.x is the module’s firmware revision.

The display then alternates between OK and port link status for both
ports.

This graphic shows the front of the module for these modules (extended-
temperature versions [catalog numbers 1756-EN2TXT and 1756-
EN2TRXT] not shown).

Install or Remove the Module
Under Power

You can install or remove this module while chassis power is applied.

LINK

LINK

LINK

LINK

NET

NET

OK

OK

32452

32452

NET

NET OK

OK

1

LNK1

LNK1 LNK2

LNK2 NET

NET OK

OK

LNK1

LNK1

1

2

LNK2

LNK2 NET

NET OK

OK

32452

32452

Single-port
Module

Dual-port
Module

LINK

LINK NET

NET

OK

OK

Single-port
Module

Dual-port
Module

WARNING: When you insert or remove the module while backplane power is
on, an electrical arc can occur. This could cause an explosion in hazardous
location installations.

Be sure that power is removed or the area is nonhazardous before proceeding.
Repeated electrical arcing causes excessive wear to contacts on both the module
and its mating connector. Worn contacts may create electrical resistance that can
affect module operation.

ATTENTION: Although the module is designed to support RIUP, when you
remove or insert the module with field-side power applied, unintended
machine motion or loss of process control can occur. Exercise extreme caution
when using this feature.