Rockwell Automation 1756-Enxxx_Ewxxx EtherNet/IP Modules Installation Instructions User Manual
Page 63
Advertising
Rockwell Automation Publication ENET-IN002F-EN-P - January 2014
63
Install a 1769 EtherNet/IP Adapter Chapter 3
5. Select the appropriate module.
6. Click Add to Relation List.
The New Entry dialog box appears.
7. Type an IP Address, Hostname, and Description for the module.
8. Click OK.
9. To permanently assign this configuration to the module, wait for the
module to appear in the Relation List panel and select it.
10. Click Disable BOOTP/DHCP.
When power is recycled, the module uses the assigned configuration and
does not issue a BOOTP request.
IMPORTANT
If you do not click Disable BOOTP/DHCP, when power is cycled, the host
controller clears the current IP configuration and begins sending
BOOTP requests again.
Advertising