Install a 1768 EtherNet/IP Communication Module Chapter 2

If you use the Rockwell Automation BOOTP or DHCP server in an uplinked
subnet where an enterprise DHCP server exists, a module may get an address
from the enterprise server before the Rockwell Automation utility even sees the
module. You might have to disconnect from the uplink to set the address and
configure the module to retain its static address before reconnecting to the
uplink. This is not a problem if you have node names configured in the module
and leave DHCP enabled.

Set the Network IP Address with RSLinx Software

Follow these steps to use RSLinx software to set the communication module’s
IP address.

1. From the Communications menu, choose RSWho.

The RSWho dialog box appears.

2. Navigate to the Ethernet network.

3. Right-click the EtherNet/IP module and choose Module Configuration.

The Module Configuration dialog box appears.

4. Click the Port Configuration tab.