1769 EtherNet/IP Adapter Status Indicators

The 1769 EtherNet/IP adapter has the following status indicators.

m

Adapter

MOD

NET

LINK 1

LINK 2

Status Indicator

Description

Status

State

Module (MOD)
Status

Indicates the module’s current state.

Off

Module does not have 24V/5V DC power.

Flashing green

Module has not been configured.

Green

Module has 24V/5V DC power.

Flashing red

Recoverable fault and/or duplicate IP address has been detected.

Red

An unrecoverable fault has been detected.

Flashing red/green

Module is performing power-up self-test.

Network (NET)
Status

Indicates the status of the module’s IP address
and connection status.

Off

Module is not powered, or does not have an IP address.

Flashing green

The adapter has an IP address, but no CIP connections are established.

Green

Module has an IP address and at least one established connection.

Flashing red

One or more of the connections in which the module is the target has
timed out.

Red

A duplicate IP address has been detected.

Link (LNK1/LNK2)
Status

Indicates the module’s current state with respect
to transmitting data on the EtherNet/IP network.

Off

No data is being transmitted.

Green

Link established at 100 Mbps. Module is ready to communicate.

Flashing green

Data transmission in progress at 100 Mbps.

Flashing Yellow

Link activity present on indicated port at 10 Mbps.

Yellow

Link established on indicated port at 10 Mbps.

Advertising