Rockwell Automation Publication ENET-IN002F-EN-P - January 2014

Appendix D Fiber Cable and LC Connector

Fiber channel power budget at rated BER
(Two connected modules or taps, either the 1756-EN2F
EtherNet/IP fiber module, or 1783-ETAP1F or 1783-
ETAP2F EtherNet/IP fiber taps)

12.8 dB for 62.5/125 µm multimode fiber
9.3 dB for 50/125 µm multimode fiber

Fiber type

Glass
62.5/125 µm and 50/125 µm multimode fiber
Simplex or duplex
Jacket type and jacket diameter is dependent on
connector selection
Graded Index (GI) fiber
Per IEC 60794-1-1, IEC 60793-2-10 category A1 fibers

Connector type

IEC 61754-20 LC connector, max. insertion loss 0.75 dB per
connection

Channel length, max

2 km (1.24 mi)

(1)

(1) The channel, that is, connectors and cable, must not exceed the allowable power budget.

IMPORTANT

Allow at least 5.08 cm (2 in.) for the fiber cable bend radius. Contact
the cable manufacturer for more information on the recommended cable
bend radius.

Table 4 - Fiber Cable and LC Connector Specifications

Attribute

Value

EXAMPLE

In the example shown here, the channel insertion loss is calculated for an optical channel based on these factors:

1 dB/km fiber

0.75 dB per adapter

Note that in this example, the end connectors are not factored in the calculations

.

ATTENTION: The maximum power budget for this example is 12.8 dB for 62.5/125

m fiber. Therefore, the channel

insertion loss for the example of 3.5 dB is less than the maximum power budget.

Fiber 1 dB/km

Fiber 1 dB/km

Fiber 1 dB/km

0.75 dB

0.75 dB

1km

0.75km

0.25km

0.75 dB

0.75 dB

0.75dB

0.25 dB

1 dB

+

+

+

+

Total channel insertion loss = 3.5 db