Chapter 2 Install a 1768 EtherNet/IP Communication Module

Reset the Module IP Address to a Factory Default Value

You can reset the module’s IP address to its factory default value by sending a
MSG instruction to the module.

For more information on resetting the network IP address to its default value
with a MSG instruction, see Knowledgebase Answer ID 55362, Reset module to
factory defaults. You can access the article at

http://rockwellautomation.custhelp.com/app/answers/list

.

Install the Module

Follow these steps to install the module.

Mount the Module with Screws

Complete these steps to install the module with screws.

1. Use the modules as a template and mark pilot holes on your panel.

2. Drill the pilot holes for M4 or #8 screws.

3. Use M4 or #8 screws to mount the modules to your panel, by using

1.16 N•m (10 lb•in) of torque.

4. Ground the module on a ground bus with a dedicated earth ground stake.

5. Connect the ground bus to a functional earth ground on the DIN rail

or panel.

Refer to Industrial Automation Wiring and Grounding Guidelines, publication

1770-4.1

, for additional information.

IMPORTANT

Do not use screws and DIN rail to mount the modules. It is possible to break
the mounting tabs off if you screw the modules to the panel while they are on
the DIN rail.