Rockwell Automation 1756-Enxxx_Ewxxx EtherNet/IP Modules Installation Instructions User Manual

Page 90

Advertising
background image

90

Rockwell Automation Publication ENET-IN002F-EN-P - January 2014

Appendix A 1756 EtherNet/IP Status Indicators

Table 1 - 1756-ENBT, 1756-EN2F, 1756-EN2T, 1756-EN2TXT, 1756-EN2TRXT, 1756-EN2TSC,1756-EWEB Modules Status Indicators

Status Indicator

Description

Status

State

Module Status Display

Alphanumeric display that scrolls messages. For example,
when a module is operating normally, the display scrolls
the module’s IP address.

N/A

N/A

Link Status (LINK)

Indicates the module’s current state with respect to
transmitting data on the EtherNet/IP network.

Off

One of these conditions exists:

The module is not powered.

Verify there is chassis power.
Verify that the module is completely inserted

into the chassis and backplane.

Make sure the module has been configured.

No link exists on the port.

Flashing green

Activity exists on the port.

Green

Activity exists on the port.

OK Status (OK)

Indicates the module’s current state. For example, this
status indicator indicates if the module is executing
power-up testing, in the process of a firmware update or
operating normally.

Off

The module is not powered.

Verify there is chassis power.

Verify that the module is completely inserted into

the chassis and backplane.

Make sure the module has been configured.

Flashing green

The module is not configured. The Module Status

display scrolls: BOOTP or
DHCP<Mac_address_of_module>
For example: BOOTP 00:0b:db:14:55:35
Configure the module.

Green

The module is operating correctly. The module’s IP

address scrolls across the Module Status display.

Flashing red

The module detected a recoverable minor fault. Check

the module configuration. If necessary, reconfigure
the module.

Red

The module detected an unrecoverable major fault.

Cycle power to the module. If this does not clear the
fault, replace the module.

Network Status (NET)

Indicates if CIP connections are established.

Off

One of these conditions exists:

The module is not powered.

Verify there is chassis power.

Verify that the module is completely inserted

into the chassis and backplane.

Make sure the module has been configured.

The module is powered but does not have an IP

address. Assign an IP address to the module.

Flashing green

The controller has an IP address and one of these

conditions exists:

The module has not established any CIP

connections.
If connections are configured for this module,
check the connection originator for the connection
error code.

One or more connections have timed out. For

example, an HMI or I/O connection has timed out.
Reestablish the connection.