Chapter 1 Prepare the Kinetix 5500 Drive Hardware

Mount the Kinetix 5500 Drive

1.

Verify that you have met the minimum clearance requirements required for mounting your
2198-H

xxx-ERS servo drive.

Additional clearance is required for cables and wires or the shared-bus connection system connected to
the top of the drive.

Additional clearance is required if other devices are installed above and/or below the drive and have
clearance requirements of their own.

Additional clearance left and right of the drive is required when mounted adjacent to noise sensitive
equipment or clean wireways.

The recommended minimum cabinet depth is 300 mm (11.81 in.).

IMPORTANT

Mount the drive in an upright position as shown. Do not mount the drive on its side.

Clearance right of the
drive is not required.

Clearance left of the

drive is not required.

Kinetix 5500

Servo Drive

40 mm (1.57 in.) clearance below

drive for airflow and installation

40 mm (1.57 in.) clearance above

drive for airflow and installation

Minimum Clearance Requirements