Mount the kinetix 5500 drive, Mount the, Kinetix 5500 – Rockwell Automation Logix5000 Control Systems: Connect Kinetix 5500 Drives on EtherNet/IP Network Quick Start User Manual
Page 14: Drive

14
Rockwell Automation Publication IASIMP-QS035A-EN-P - December 2012
Chapter 1 Prepare the Kinetix 5500 Drive Hardware
Mount the Kinetix 5500 Drive
1.
Verify that you have met the minimum clearance requirements required for mounting your
2198-H
xxx-ERS servo drive.
•
Additional clearance is required for cables and wires or the shared-bus connection system connected to
the top of the drive.
•
Additional clearance is required if other devices are installed above and/or below the drive and have
clearance requirements of their own.
•
Additional clearance left and right of the drive is required when mounted adjacent to noise sensitive
equipment or clean wireways.
•
The recommended minimum cabinet depth is 300 mm (11.81 in.).
IMPORTANT
Mount the drive in an upright position as shown. Do not mount the drive on its side.
Clearance right of the
drive is not required.
Clearance left of the
drive is not required.
Kinetix 5500
Servo Drive
40 mm (1.57 in.) clearance below
drive for airflow and installation
40 mm (1.57 in.) clearance above
drive for airflow and installation
Minimum Clearance Requirements