Chapter 2 Add a Kinetix 5500 Drive to a Logix Designer Application

4.

In the Test Distance field, type 2.0 as the number of revolutions for the test.

5.

Click the desired tab (Marker/Motor Feedback/Motor and Feedback).

In this example, the Motor and Feedback test is chosen.

6.

Click Start.

The Logix Designer - Motor and Feedback Test dialog box
opens. The Test State is Executing.

TESTING appears on the drive LCD display.

When the test completes successfully, the Test State changes
from Executing to Passed.

7.

Click OK.

This dialog box opens asking if the direction was correct.

8.

Click Yes.

9.

Click Accept Test Results.

10.

If the test fails, this dialog box opens.
a. Click OK.
b. Verify the DC bus voltage.
c. Verify unit values entered in the Scaling category.
d. Return to

step 5

and run the test again.

Test

Description

Marker

Verifies marker detection capability as you rotate the motor
shaft.

Motor Feedback

Verifies feedback connections are wired correctly as you rotate
the motor shaft.

Motor and Feedback

Verifies motor power and feedback connections are wired
correctly as you command the motor to rotate.

TESTING

192.168.1.1

DC BUS: 218.3V

SETUP

MENU

Drive LCD Display