Wire the input power connector, L3 l2 l1 – Rockwell Automation Logix5000 Control Systems: Connect Kinetix 5500 Drives on EtherNet/IP Network Quick Start User Manual

Page 20

Advertising
background image

20

Rockwell Automation Publication IASIMP-QS035A-EN-P - December 2012

Chapter 1 Prepare the Kinetix 5500 Drive Hardware

Wire the Input Power Connector

The input power (IPD) connector requires 195…528V AC (single-phase or three-phase) for mains input power.

Input Power (IPD) Connector Specifications

ATTENTION: Make sure the input power connections are correct when wiring the IPD connector plug and that the plug is fully
engaged in the drive connector. Incorrect wiring/polarity or loose wiring can cause explosion or damage to equipment.

Kinetix 5500 Drive
Cat. No.

Pin

Signal

Recommended
Wire Size
mm

2

(AWG)

Strip Length
mm (in.)

Torque Value
N•m (lb•in)

2198-H003-ERS
2198-H008-ERS
2198-H015-ERS
2198-H025-ERS
2198-H040-ERS

1.5…4
(16…12)

8.0 (0.31)

0.5…0.6
(4.4…5.3)

2198-H070-ERS

1.5…6
(16…10)

L3

L2

L1

Remo

ve

For DC

Bus O

nly

Kinetix 5500 Drive
Top View

Input Power (IPD) Connector Plug

L3
L2
L1

L3
L2
L1

Advertising